3-6 Network Cabling and Base Plate Installation
Power Cabling Requirements in AWG (Continued)
Load (VA)
Feet
10 15 20 25 30 40 55 75 100 130 180 200
340 22 22 22 20 20 18 18 16 14 14 12 12
365 22 22 22 20 20 18 16 16 14 14 12 12
375 22 22 22 20 20 18 16 16 14 12 12 12
395 22 22 20 20 20 18 16 16 14 12 12
400 22 22 20 20 18 18 16 16 14 12 12
420 22 22 20 20 18 18 16 14 14 12 12
470 22 22 20 20 18 18 16 14 14 12
475 22 22 20 20 18 16 16 14 14 12
500 22 22 20 18 18 16 16 14 12 12
545 22 20 20 18 18 16 16 14 12 12
580 22 20 20 18 18 16 14 14 12 12
595 22 20 20 18 18 16 14 14 12
630 22 20 18 18 18 16 14 14 12
635 22 20 18 18 16 16 14 14 12
750 22 20 18 18 16 16 14 12 12
755 20 20 18 18 16 14 14 12 12
795 20 20 18 16 16 14 14 12
865 20 18 18 16 16 14 14 12
945 20 18 18 16 16 14 12 12
1000 20 18 16 16 16 14 12 12
1010 20 18 16 16 14 14 12 12
1190 20 18 16 16 14 14 12
1200 18 18 16 16 14 12 12
1260 18 18 16 14 14 12 12
1375 18 16 16 14 14 12 12
1500 18 16 16 14 14 12
1590 18 16 14 14 14 12
1645 18 16 14 14 12 12