User's Manual
ANSI Electric Meter v3.1 User’s Guide 89
Appendix D
Model Changes
Model 83011-83301 Changes
The following describes significant changes to model 83011-83301 of the Echelon
electric ANSI meter as compared to the previous model (83010 through 83300), and
any additional significant changes to this document.
Item Added or Changed Reference Pages
Test mode is an optional feature that is only supported by
some NES version 3.1 ANSI meters. While in test mode, the
meter will suspend standard energy accumulations, standard
demand calculations, power quality analysis, tariff register
calculations, automated control of the disconnect switch, and
automated control of the control relay. You may find test mode
useful if you want to test the meter’s accuracy without
disrupting its billing registers. Test mode can be activated with
a push button on the meter front panel.
“Test Mode” on page 1
The meter display has been updated to:
Allow the user to configure whether or not, and for how
long, the present firmware version will be displayed
when the meter is powered on.
Include new display icons and diagnostic messages
relevant to new features such as test mode, the tilt
sensor, demand metering, as well as new icons
intended to enhance the information displayed for
other meter features such as the load disconnect
contactor.
Allow the user to select the format in which the current
date will be shown on the meter display.
Display various reasons the load disconnect contactor
has been opened or closed, as a user-supplied text
string.
Allow disabling of the automatic scroll feature.
“Reading the Display” on page 1 and “Self
Tests and Diagnostic Messages” on page
1
The meter now provides power quality measurements for
harmonic distortion. In addition, you can now configure a
threshold level that determines when a phase loss event will
logged in the event log.
“Power Quality” on page 1
New status and alarm events are available to be logged in the
meter event log.
“Event Log” on page 1