ECN 7000 Series Hardware Guide 53
Figure 27. Battery Pack Restraining Tab
To replace the battery pack:
1. Insert the battery pack into the battery compartment. The restraining
tab must be oriented toward the ECN cover. The restraining tab will
click into place.
2. Ensure that the battery pack’s gasket makes a good seal with the battery
compartment.
3. Insert and tighten the four sealing screws. Tighten the screws in a
diagonal “X” pattern (alternating top-left, bottom-right, top-right, bottom-
left). Tighten the screws to no more than 9.1 (±0.4) lbf-in (10.4 [±0.5] kgf-
cm) torque.