Datasheet

AC axial compact fan
sickle-shaped blades (S series)
W2E250-HL06-01
Curves: Air performance 50 Hz
Druck p f s[Pa]für Rho=1,2kg/m^3
qv[m^3/h]
2.2002.0001.8001.6001.4001.2001.0008006004002000
qv[cfm]
1.2001.0008006004002000
p f s[Pa]
230
220
210
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
pfs _E[IN H2O]
0,9
0,85
0,8
0,75
0,7
0,65
0,6
0,55
0,5
0,45
0,4
0,35
0,3
0,25
0,2
0,15
0,1
0,05
0
p f s[Pa]
1
2
3
4
Measurement: LU-59959-1
Air performance measured according to ISO
5801 installation category A. For detailed
information on the measurement setup,
contact ebm-papst. Intake sound level:
Sound power level according to ISO 13347 /
sound pressure level measured at 1 m
distance from fan axis. The values given are
valid under the specified measuring
conditions and may vary due to conditions of
installation. For deviations from the standard
configuration, the parameters have to be
checked on the installed unit.
Measured values
1
2
3
4
U
V
230
230
230
230
f
Hz
50
50
50
50
n
min
-1
2550
2485
2440
2385
P
e
W
127
136
141
146
I
A
0.56
0.59
0.61
0.63
q
V
m
3
/h
1865
1690
1530
1275
p
fs
Pa
0
40
70
100
q
V
cfm
1100
995
900
750
p
fs
inH2O
0.00
0.16
0.28
0.40
U = Power supply · f = Frequency · n = Speed (rpm) · P
e
= Power consumption · I = Current draw · q
V
= Air flow · p
fs
= Pressure increase
Item no. 10763-5-9980 · ENU · Change 88948 · Approved 2016-08-25 · Page 4 / 5