Datasheet
Product Data Sheet RG190-39/18/2TDMLO
01/31/2019 page 7 of 14
3.2 Electrical Operating Data
Measurement
conditions:
Normal air density = 1,2 kg/m3; Temperature 23°C +/ - 3°C; Motor axis horizontal; warm-up
time before measuring 5 minutes (unless otherwise specified). In the intake and outlet area
should not be any solid obstruction within 0,5 m.
∆p = 0:
corresp. to free air flow (see chapter aerodynamics)
I:
corresp. to arithm. mean current value
Name Condition
U Contr. 0001 U Contr.: 10 V
The data at 5V are no FK features and need not be tested.
Features Condition Symbol Values
Voltage range U 36 V 57 V
Nominal voltage U
N
48 V
Power consumption 41 W 58 W 54 W
+- 10 % +- 10,0 % +- 10,0 %
Tolerance
∆p = 0
U Contr. 0010
P
Current consumption 1.130 mA 1.200 mA 950 mA
+- 10,0 % +- 10,0 % +- 10,0 %
Tolerance
∆p = 0
U Contr. 0010
I
Speed 2.740 1/min 3.000 1/min 3.000 1/min
+- 10,0 % +- 5,0 % +- 5,0 %
Tolerance
∆p = 0
U Contr. 0010
n
Starting current
consumption
1.500 mA