Datasheet

Product Data Sheet RG160-28/18NTDI
02/02/2019 page 5 of 11
3.2 Electrical Operating Data
Measurement
conditions:
Normal air density = 1,2 kg/m3; Temperature 23°C +/ - 3°C; Motor axis horizontal; warm-up
time before measuring 5 minutes (unless otherwise specified). In the intake and outlet area
should not be any solid obstruction within 0,5 m.
p = 0:
corresp. to free air flow (see chapter aerodynamics)
I:
corresp. to arithm. mean current value
Name Condition
TU 0001 TU: >= 50 °C
NTC 0001
Features Condition Symbol Values
Voltage range U 38 V 57 V
Nominal voltage U
N
48 V
Power consumption 39,9 W 59 W 54,2 W
+- 17,5 % +- 12,5 % +- 15,0 %
Tolerance
p = 0
TU / NTC
0010
P
Current consumption 1.050 mA 1.200 mA 950 mA
+- 17,5 % +- 12,5 % +- 15,0 %
Tolerance
p = 0
TU / NTC
0010
I
Speed 3.850 1/min 4.200 1/min 4.200 1/min
+- 12,5 % +- 7,5 % +- 10,0 %
Tolerance
p = 0
TU / NTC
0010
n
Motor testing
The motor testing relates to a fan, operating with horizontal shaft, at free wir flow. It is possible to run this motor in an
uncontrolled state. For some testings the motor may set in a test cycle by connecting to a voltage follower as below
mentioned.
Voltage graph to start the test cycle