Datasheet
Product Data Sheet RER175-42/14/2TDMP
01/31/2019 page 6 of 13
Information to the curve:
0 % - 7% PWM: 0 1/min
7 % - 10% PWM: 800 1/min (corresponding to min. speed)
10 % - 90% PWM: linear increasing curve
90 % - 100% PWM: 4.800 1/min (corresponding to max. speed)
7 % PWM: 800 1/min (Fan on, comming from 0% PWM)
5 % PWM: 600 1/min bzw. 0 1/min (Fan off, comming from 100% PWM)
3.2 Electrical Operating Data
Measurement
conditions:
Normal air density = 1,2 kg/m3; Temperature 23°C +/ - 3°C; Motor axis horizontal; warm-up
time before measuring 5 minutes (unless otherwise specified).
In the intake and outlet area should not be any solid obstruction within 0,5 m.
Measurement setup: Measured between two steel plates
Steel plate: 180 mm x 180 mm
Intake nozzle: D: 125,5 mm; R: 10 mm
Distance between bottom and top plate: 80 mm
Overlapping impeller / nozzle: 2 mm
∆p = 0: corresp. to free air flow (see chapter aerodynamics)
I: corresp. to arithm. mean current value
Name Condition
PWM 0001 PWM: 100 %; f: 2 kHz
100% PWM; f = 2 kHz or broken lead wire (open control input)
Features Condition Symbol Values
Voltage range U 16 V 36,0 V
Nominal voltage U
N
24,0 V
Power consumption 63,0 W 110 W 112,0 W
+- 10,0 % +- 10,0 % +- 10,0 %
Tolerance
∆p = 0
PWM 0010
P
Current consumption 3.930 mA 4.600 mA 3.050 mA
+- 10,0 % +- 10,0 % +- 10,0 %
Tolerance
∆p = 0
PWM0010
I
Speed 4.020 1/min 4.860 1/min 4.860 1/min
+- 10,0 % +- 10,0 % +- 10,0 %
Tolerance
∆p = 0
PWM 0010
n