Product Data Sheet RER175-42/14/2TDMLPU Product Data Sheet RER175-42/14/2TDMLPU The engineer's choice
Product Data Sheet RER175-42/14/2TDMLPU RER175-42/14/2TDMLPU INDEX 1 General ............................................................................................................................................................... 3 2 Mechanics .......................................................................................................................................................... 3 2.1 2.2 3 Operating Data ........................................................................
Product Data Sheet RER175-42/14/2TDMLPU 1 General Fan type Rotating direction looking at rotor Airflow direction Bearing system Mounting position - shaft 2 Mechanics 2.1 General Depth Diameter Mass Housing material Impeller material 2.
Product Data Sheet RER175-42/14/2TDMLPU The auxilliaries shown on the schematic diagram (which are required for the intended use) are not part of our delivery.
Product Data Sheet RER175-42/14/2TDMLPU 3 Operating Data 3.1 Electrical Interface - Input Control input PWM Features Inpute type PWM - Frequency Open collector 1 kHz - 20 kHz typical: 2 kHz Characteristics Schematics Speed control: By Puls width modulation (PWM) 0 ...
Product Data Sheet RER175-42/14/2TDMLPU Information to the curve: 0 % - 7% PWM: 0 1/min 7 % PWM: 800 1/min (Fan on, comming from 0% PWM) 7 % - 10% PWM: 800 1/min (corresponding to min. speed) 10 % - 90% PWM: linear increasing curve 90 % - 100% PWM: 3.400 1/min (corresponding to max. speed) 7 % - 5 % PWM: linear decreasing curve (comming from 100% PWM) 5 % PWM: 600 1/min or 0 1/min (Fan off, comming from 100% PWM) 3.
Product Data Sheet RER175-42/14/2TDMLPU 3.3 Electrical Interface - Output Tacho type /2 (open collector) Please note: At zero speed the tacho signal is at a static HIGH. It will be also HIGH when the fan is still spinning, but the speed control signal is set to zero speed already. The tacho signal is only activated after the start-up is completed.
Product Data Sheet RER175-42/14/2TDMLPU Max. residual current at UN Locked rotor protection Locked rotor current at UN Clock signal at locked rotor IF <= 5 mA Auto restart Iblock approx. 3.400 mA t3 / t4 typical: 6,5 s / 10 s Locked rotor signal t5: After 4 failed start-ups there is an extended timeout of 40 s.
Product Data Sheet RER175-42/14/2TDMLPU 3.5 Aerodynamics Measurement conditions: Measured with a double chamber intake rig acc. to DIN EN ISO 5801. Normal air density = 1,2 kg/m3; Temperature 23°C +/ - 3°C; In the intake and outlet area should not be any solid obstruction within 0,5 m. Motor shaft horizontal. The information is only valid under the specified test conditions and may be changed by the installation conditions.
Product Data Sheet RER175-42/14/2TDMLPU 01/31/2019 page 10 of 14
Product Data Sheet RER175-42/14/2TDMLPU 3.6 Sound Data Measurement conditions: Sound pressure level: 1 meter distance between microphone and the air intake. Sound power level: Acc. to DIN 45635 part 38 (ISO 10302) Measured in a semianchoic chamber with a background noise level of Lp(A) < 5 dB(A) For further measurement conditions see chapter aerodynamics. a.) Operation condition: 3.
Product Data Sheet RER175-42/14/2TDMLPU Please require severity levels and specification parameters from the responsible development departments.
Product Data Sheet RER175-42/14/2TDMLPU 5 Safety 5.1 Electrical Safety Dielectric strength DIN EN 60950 (VDE 0805) and DIN EN 60335 (VDE 0700) A.) Type test Measuring conditions: After 48h of storage at 95% R.H. and 25°C. No arcing or breakdown is allowed! All connections together to ground. B.) Routine test Measuring conditions: At indoor climate. No arcing or breakdown is allowed! All connections together to ground. Isolation resistance Measuring conditions: After 48h of storage at 95% R.H.