02/01/2019 page 10 of 14
3.5 Aerodynamics
Measurement
conditions:
Measured with a double chamber intake rig acc. to DIN EN ISO 5801.
Normal air density = 1,2 kg/m3; Temperature 23°C +/ - 3°C;
In the intake and outlet area should not be any solid obstruction within 0,5 m. Motor shaft
horizontal.
The information is only valid under the specified test conditions and may be changed by the
installation conditions. If there are deviations from the standard test conditions, the
characteristic values must be checked under the installed conditions.
Measurement setup: Measured between two steel plates
Steel plate: 180 mm x 180 mm
Intake nozzle: D: 125,5 mm; R: 10 mm
Distance between bottom and top plate: 80 mm
Overlapping impeller / nozzle: 2 mm
a.) Operation condition:
3.400 1/min at free air
flow
PWM 95 %; f: 2 kHz
Max. free-air flow (∆p = 0 /
= max.) 590,0 m3/h
Max. static pressure (∆p = max. /
=0) 400 Pa