Datasheet

Product Data Sheet RER120-26/18/2TDMP-005
02/01/2019 page 5 of 12
Information to the curve:
0 % - 7% PWM: 0 1/min
7 % - 10% PWM: 800 1/min (corresponding to min. speed)
10 % - 90% PWM: linear increasing curve
90 % - 100% PWM: 5.200 1/min (corresponding to max. speed)
7 % PWM: 800 1/min (Fan on, comming from 0% PWM)
5 % PWM: 600 1/min bzw. 0 1/min (Fan off, comming from 100% PWM)
3.2 Electrical Operating Data
Measurement
conditions:
Normal air density = 1,2 kg/m3; Temperature 23°C +/ - 3°C; Motor axis horizontal; warm-up
time before measuring 5 minutes (unless otherwise specified).
In the intake and outlet area should not be any solid obstruction within 0,5 m.
Measurement setup: Measured between two steel plates
Steel plate: 140 mm x 140 mm
Intake nozzle: D: 96 mm; R: 16 mm
Distance between bottom and top plate: 70 mm
Overlapping impeller / nozzle: 2 mm
p = 0: corresp. to free air flow (see chapter aerodynamics)
I: corresp. to arithm. mean current value
Name Condition
PWM 0001 PWM: 100 %; f: = 2 kHz
100% PWM or broken lead wire (open control input)
The data at 50%PWM are no FK features and need not be tested.
Features Condition Symbol Values
Voltage range U 36 V 60 V
Nominal voltage U
N
48 V
Power consumption 40 W 53 W 52 W
+- 10,0 % +- 10,0 % +- 10,0 %
Tolerance
p = 0
PWM 0010
P
Current consumption 1.100 mA 1.100 mA 860 mA
+- 10,0 % +- 10,0 % +- 10,0 %
Tolerance
p = 0
PWM0010
I
Speed 4.780 1/min 5.200 1/min 5.200 1/min
+- 5 % +- 5 % +- 5 %
Tolerance
p = 0
PWM 0010
n