Datasheet

Product Data Sheet 8314 N/2H3P
01/31/2019 page 6 of 11
Schematics
3.2 Electrical Operating Data
Measurement
conditions:
Normal air density = 1,2 kg/m3; Temperature 23°C +/ - 3°C; Motor axis horizontal; warm-up
time before measuring 5 minutes (unless otherwise specified). In the intake and outlet area
should not be any solid obstruction within 0,5 m.
p = 0:
corresp. to free air flow (see chapter aerodynamics)
I:
corresp. to arithm. mean current value
Name Condition
PWM 0001 PWM: 100 %; f: 25 kHz
Features Condition Symbol Values
Voltage range U 18 V 26,4 V
Nominal voltage U
N
24 V
Power consumption 4,5 W 8,9 W 10,5 W
+- 17,5 % +- 12,5 % +- 15,0 %
Tolerance
p = 0
PWM 0010
P
Current consumption 250 mA 370 mA 398 mA
+- 17,5 % +- 12,5 % +- 15,0 %
Tolerance
p = 0
PWM 0010
I
Speed 6.000 1/min 7.600 1/min 8.100 1/min
+- 12,5 % +- 7,5 % +- 10,0 %
Tolerance
p = 0
PWM 0010
n
Starting current
consumption
<= 2.100 mA