Datasheet

Product Data Sheet 5314/2TDHP
02/02/2019 page 6 of 13
7 % PWM: 1.000 1/min (Fan on, comming from 0% PWM)
7 % - 10% PWM: 1.000 1/min (corresponding to min. speed)
10 % - 90% PWM: linear increasing curve
90 % - 100% PWM: 6.000 1/min (corresponding to max. speed)
7 % - 5 % PWM: linear decreasing curve (comming from 100% PWM)
5 % PWM: 800 1/min or 0 1/min (Fan off, comming from 100% PWM)
3.2 Electrical Operating Data
Measurement
conditions:
Normal air density = 1,2 kg/m3; Temperature 23°C +/ - 3°C; Motor axis horizontal; warm-up
time before measuring 5 minutes (unless otherwise specified). In the intake and outlet area
should not be any solid obstruction within 0,5 m.
p = 0:
corresp. to free air flow (see chapter aerodynamics)
I:
corresp. to arithm. mean current value
Name Condition
PWM 0001 PWM: 100 %; f: 2 kHz
100% PWM; f = 2 kHz or broken lead wire (open control input)
Features Condition Symbol Values
Voltage range U 16 V 36 V
Nominal voltage U
N
24 V
Power consumption 24,5 W 41 W 43,2 W
+- 17,5 % +- 15 % +- 15 %
Tolerance
p = 0
PWM 0010
P
Current consumption 1.530 mA 1.700 mA 1.200 mA
+- 17,5 % +- 15 % +- 15 %
Tolerance
p = 0
PWM 0010
I
Speed 4.950 1/min 6.000 1/min 6.000 1/min
+- 15 % +- 5 % +- 5 %
Tolerance
p = 0
PWM 0010
n