Datasheet

Product Data Sheet 4656 ZW
04/10/2014 page 7 of 9
3.5 Sound Data
Measurement
conditions:
Sound pressure level: 1 Meter distance between microphone and the air intake.
Sound power level: Acc. to DIN 45635 part 38 (ISO 10302)
Measured in a semianchoic chamber with a background noise level of Lp(A) < 5 dB(A)
For further measurement conditions see section 3.4
a.) Operation condition:
2.650 1/min at free air flow Frequency: 50 Hz
Optimal operating point 130,0 m3/h @ 15 Pa
Sound power level at the optimal operating
point
5,1 bel(A)
Sound pressure level at free air flow,
measured in rubber bands
37,0 dB(A)
b.) Operation condition:
3.100 1/min at free air flow Frequency: 60 Hz
Optimal operating point 148,0 m3/h @ 20 Pa
Sound power level at the optimal operating
point
5,5 bel(A)
Sound pressure level at free air flow,
measured in rubber bands
42,0 dB(A)
4 Environment
4.1 General
Min. permitted ambient temperature TU min.
-40 °C / 50 Hz
-40 °C / 60 Hz
Max. permitted ambient temperature TU max.
75 °C / 50 Hz
85 °C / 60 Hz
Min. permitted storage temperature TL min. -40 °C
Max. permitted storage temperature TL max. 100 °C
4.2 Climatic requirements*)
Humidity requirements humid heat, constant; according to DIN EN 60068-2-
78, 14 days
Water exposure None
Radiation exposure None
Dust requirements None
Salt fog requirements None
Harmful gas requirements None
*) Permittet application area:
The product is intended for use in sheltered rooms with controlled temperature and controlled humidity. Directly
exposure to water must be avoided.
Pollution degree 1 (according DIN EN 60664-1)
There is either no pollution or it occurs only dry, non-conductive pollution. The pollution has no negative impact.