Datasheet
Product Data Sheet 4418 L
02/01/2019 page 4 of 9
3 Operating Data
3.1 Electrical Operating Data
Measurement
conditions:
Normal air density = 1,2 kg/m3; Temperature 23°C +/ - 3°C; Motor axis horizontal; warm-up
time before measuring 5 minutes (unless otherwise specified). In the intake and outlet area
should not be any solid obstruction within 0,5 m.
∆p = 0:
corresp. to free air flow (see chapter aerodynamics)
I:
corresp. to arithm. mean current value
Features Condition Symbol Values
Voltage range U 36 V 60 V
Nominal voltage U
N
48 V
Power consumption 1,5 W 2,5 W 4,4 W
+- 17,5 % +- 12,5 % +- 15 %
Tolerance
∆p = 0
0010
P
Current consumption 42 mA 52 mA 73 mA
+- 17,5 % +- 12,5 % +- 15 %
Tolerance
∆p = 0
0010
I
Speed 2.150 1/min 2.700 1/min 3.400 1/min
+- 12,5 % +- 7,5 % +- 10 %
Tolerance
∆p = 0
0010
n
Starting current
consumption
< 400 mA
3.2 Electrical Features
Electronic function None
Reversed polarity protection Rectifying diode
Max. residual current at U
N
I
F
< 100 uA
Locked rotor protection Auto restart
Locked rotor current at U
N
I
block
approx. 400 mA
Clock signal at locked rotor
t
3
/ t
4
typical: 0,5 s / 2,8 s