Datasheet

Product Data Sheet 414 J/2HH
07/05/2017 page 4 of 9
3 Operating Data
3.1 Electrical Operating Data
Measurement
conditions:
Normal air density = 1,2 kg/m3; Temperature 23°C +/- 3°C; Motor axis horizontal; warm-up
time before measuring 5 minutes (unless otherwise specified). In the intake and outlet area
should not be any solid obstruction within 0,5 m.
p = 0:
corresp. to free air flow (see chapter aerodynamics)
I:
corresp. to arithm. mean current value
Features
Condition
Values
Voltage range U 18 V 27 V
Nominal voltage U
N
24 V
Power consumption
p = 0
0010
P
2 W 3,6 W 4,5 W
Tolerance
+- 20 % +- 20 % +- 20 %
Current consumption
p = 0
0010
I
110 mA 150 mA 165 mA
Tolerance
+- 20 % +- 20 % +- 20 %
Speed
p = 0
0010
n
10.200 1/min 13.000 1/min 14.100 1/min
Tolerance
+- 15 % +- 15 %
Starting current
consumption
1.100 mA