Datasheet
Product Data Sheet 4118 N/2H7P
02/01/2019 page 6 of 16
Transistor requirements: VCE max. >= 12V; Isink max > 5mA; VCEsat < 0,15V
Alternatively to the PWM signal the fan can be controlled by an analog control signal of 0...5 V (5 V corresponds to
100 % PWM)
It must be ensured that the power supply is "sink-able" and can operate with the internal pull-up resistor.
The shown pull-up resistor to the internal reference voltage (+5V) has 10kOhm.
3.2 Electrical Operating Data
Measurement
conditions:
Normal air density = 1,2 kg/m3; Temperature 23°C +/ - 3°C; Motor axis horizontal; warm-up
time before measuring 5 minutes (unless otherwise specified). In the intake and outlet area
should not be any solid obstruction within 0,5 m.
∆p = 0:
corresp. to free air flow (see chapter aerodynamics)
I:
corresp. to arithm. mean current value
Name Condition
PWM 0001 PWM: 95 %; f: 2 kHz
Attention!
The inrush current depends on the capacitor and the resistance of the wires. When using an external capacitor the
inrush current rises accordingly. The integrated capacitor has 47uF.
Features Condition Symbol Values
Voltage range U 36 V 60 V
Nominal voltage U
N
48 V
Power consumption 53 W 90 W 82,0 W
+- 12,5 % +- 10 % +- 10 %
Tolerance
∆p = 0
PWM 0010
P
Current consumption 1.450 mA 1.900 mA 1.370 mA
+- 12,5 % +- 10 % +- 10 %
Tolerance
∆p = 0
PWM 0010
I
Speed 8.300 1/min 9.500 1/min 9.500 1/min
+- 7,5 % +- 5 % +- 5 %
Tolerance
∆p = 0
PWM 0010
n