Data Sheet

AC axial compact fan
W2S130-BM03-01
Charts: Air flow 60 Hz
qv m³/h
cfm
Pfs
Pa
in wg
100 200 300 400
0 50 100 150 200 250
20
40
60
80
0.05
0.1
0.15 0.2 0.25 0.3 0.35
1
2
3
4
ρ = 1.15 kg/m³ ± 2 %
Measurement: LU-57322-1
Air performance measured as per ISO 5801
Installation category A. For detailed
information on the measuring set-up, please
contact ebm-papst. Suction-side noise
levels: LwA measured as per ISO 13347 /
LpA measured with 1m distance to fan axis.
The values given are valid under the
measuring conditions mentioned above and
may vary according to the actual installation
situation. With any deviation from the
standard set-up, the specific values have to
be checked and reviewed with the unit
installed.
Measured values
1
2
3
4
U
V
230
230
230
230
f
Hz
60
60
60
60
n
min
-1
3050
3035
2975
2940
P
e
W
46
50
51
52
I
A
0.27
0.28
0.29
0.29
q
V
m
3
/h
435
390
340
255
p
fs
Pa
0
25
50
75
q
V
cfm
255
230
200
150
p
fs
in. wg
0.00
0.10
0.20
0.30
U = Supply voltage · f = Frequency · n = Speed (rpm) · P
e
= Power input · I = Current draw · q
V
= Air flow · p
fs
= Pressure increase
Item no. 10946-5-9980 · ENG · Revision 99022 · Release 2018-04-26 · Page 5 / 5