Data Sheet

AC axial compact fan
W2S130-AA03-01
Charts: Air flow 60 Hz
qv m³/h
cfm
Pfs
Pa
in wg
50 100 150 200 250 300 350
0 40 80 120 160 200
20
40
60
80
0.05
0.1 0.15 0.2 0.25 0.3
1
2
3
4
ρ = 1.15 kg/m³ ± 2 %
Measurement: LU-58476-1
Air performance measured as per ISO 5801
Installation category A. For detailed
information on the measuring set-up, please
contact ebm-papst. Suction-side noise
levels: LwA measured as per ISO 13347 /
LpA measured with 1m distance to fan axis.
The values given are valid under the
measuring conditions mentioned above and
may vary according to the actual installation
situation. With any deviation from the
standard set-up, the specific values have to
be checked and reviewed with the unit
installed.
Measured values
1
2
3
4
U
V
230
230
230
230
f
Hz
60
60
60
60
n
min
-1
3250
3200
3165
3145
P
e
W
39
42
43
44
I
A
0.25
0.25
0.26
0.26
q
V
m
3
/h
390
355
305
235
p
fs
Pa
0
25
50
70
q
V
cfm
230
210
180
135
p
fs
in. wg
0.00
0.10
0.20
0.28
U = Supply voltage · f = Frequency · n = Speed (rpm) · P
e
= Power input · I = Current draw · q
V
= Air flow · p
fs
= Pressure increase
Item no. 10434-5-9980 · ENG · Revision 99006 · Release 2018-04-26 · Page 5 / 5