Data Sheet
Product Data Sheet QG030-198/12
02/06/2019 page 4 of 8
3 Operating Data
3.1 Electrical Operating Data
Measurement
conditions:
Normal air density = 1,2 kg/m3; Temperature 23°C +/- 3°C; Motor axis horizontal;warm-up
time before measuring 5 minutes (unless otherwise specified).In the intake and outlet area
should not be any solid obstruction within 0,5 m.
∆p = 0:
corresp. to free air flow (see chapter aerodynamics)
I:
corresp. to arithm. mean current value
Features
Condition
Symbol
Values
Voltage range
∆p = 0
U
8,0 V
14,0 V
Nominal voltage
∆p = 0
U
N
12,0 V
Power consumption
∆p = 0
P
8,0 W
7,7 W
Tolerance
+- 10 %
+- 10 %
Current consumption
∆p = 0
I
665 mA
550 mA
Tolerance
+- 10 %
+- 10 %
Speed
∆p = 0
n
3.000 1/min
4.400 1/min
4.900 1/min
Tolerance
+- 7,5 %
+- 7,5 %
+- 7,5 %
3.2 Electrical Features
Electronic function
None
Reversed polarity protection
PTC
Max. residual current at Umax
IF 5.000 mA
reaction time reversed polarity protection
< 30,0 s at Tu = 23°C
Locked rotor protection
PTC
reaction time locked roter protection
< 300 s at Tu = 23°C
Locked rotor current at Umax
approx. 300 mA according 120 s
Blower restart possible after a short power shut down.