Data Sheet
Product Data Sheet 4500 N
   01/31/2019  page 7 of 9 
3.4  Sound Data 
Measurement 
conditions: 
Sound pressure level: 1 meter distance between microphone and the air intake. 
Sound power level: Acc. to DIN 45635 part 38 (ISO 10302)Sound power level: Acc. to DIN 
45635 part 38 (ISO 10302) 
Measured in a semianchoic chamber with a background noise level of Lp(A) < 5 dB(A) 
For further measurement conditions see chapter aerodynamics. 
a.) Operation condition: 
2.550 1/min at free air flow 
Frequency: 50 Hz 
Optimal operating point 
76,0 m3/h @ 27 Pa 
Sound power level at the optimal operating 
point 
5,5 bel(A) 
Sound pressure level at free air flow, 
measured in rubber bands 
45,0 dB(A) 
b.) Operation condition: 
3.000 1/min at free air flow 
Frequency: 60 Hz 
Optimal operating point 
92,0 m3/h @ 30 Pa 
Sound power level at the optimal operating 
point 
5,6 bel(A) 
Sound pressure level at free air flow, 
measured in rubber bands 
48,0 dB(A) 
4  Environment 
4.1  General 
Min. permitted ambient temperature TU min. 
-10 °C / 50 Hz 
-10 °C / 60 Hz 
Max. permitted ambient temperature TU max. 
55 °C / 50 Hz 
65 °C / 60 Hz 
Min. permitted storage temperature TL min. 
-40 °C 
Max. permitted storage temperature TL max. 
80 °C 
4.2  Climatic Requirements*) 
Humidity requirements 
humid heat, constant; according to DIN EN 60068-2-
78, 14 days 
Water exposure 
None 
Dust requirements 
None 
Salt fog requirements 
None 
Permitted application area: 
The product is intended for use in sheltered rooms with controlled temperature and controlled humidity. Directly 
exposure to water must be avoided. 
Pollution degree 1 (according DIN EN 60664-1) 
There is either no pollution or it occurs only dry, non-conductive pollution. The pollution has no negative impact. 