User manual

Application and function
The compact TS+ Thermal Actuator covers a wide 
range of control and regulating applications in 
heating, cooling and air circulation. Applications 
include:
•  Individual room controls for underoor heating 
systems and radiators
•  Zone controls
•  Multi-circuit regulators  for one and two  pipe 
systems
Features
• 230 V and 24 V variants
•  Normally closed
•  Manual position (to open valve by hand)
•  can be mounted in any direction 
(even upsidedown)
•  Silent operation
•  Stroke position is visible under the cover
•  Compact and stylish construction
Dimensional drawing
Technical Data
For 230 V version TS+ 5.11
Supply voltage  230 V AC 50 Hz
Inrush current  <1A
Opening time  3 - 4 Min.
Power Consumption  2.5 W
For 24 V version TS+ 6.11
Supply voltage  24 V AC
Inrush current  <0.5A
Opening time  5 Min.
Power Consumption  2.5 W
For both versions:
Actuator type Normally closed
Ingress Protection IP 54
Isolation Class II
Stroke length 4.5 mm
Closing force 90 N or 120 N
Closing time 2-3 mins
Valve connection M 30/M 28x1.5 mm
Weight ~120 g
Operating temperature 0 … 50 °C
Storage temperature –25 … 70 °C
Shock load voltage 2.5 KV
Temperature for
Ball Pressure Test
100 °C
Voltage and Current for 
EMC Test
230 V, 0,1 A
Installation and
commissioning instructions
Thermal Actuator
TS+
Mounting and Installation
1. The  TS+  should  be  mounted  in  the
manually-open position (as supplied)  
– see Picture 3
2.  Screw the TS+ onto the valve. Hand tighten
only
3.  Press and turn  the  cover clockwise until the 
click position. The markings on the TS+ should 
line up (see Picture 4)
NOTE:the TS+ will only work properly in the clo-
sed position (see Picture 4)
Electrical Connection
WARNING: Disconnect from mains
before installing
Connections according to wiring diagram:
WARNING:
The  TS+  should  only  be  installed  by  a
suitably-qualied person. 
All valid health and safety regulations must 
also be complied with.
The Thermal Actuator TS+ is suitable for the 
opening and closing of valves in dry and en-
closed rooms in normal ambient conditions. 
The product conforms to EN 60730.
Function
The Actuator opens the valve when electrically 
activated. This call for heat normally comes from 
a control device (thermostat). Without power the 
TS+ closes automatically
The  current  position  of  the  valve  can  be  seen 
using the position indicator:
Valve  Valve
Open  Closed
Picture 1  Picture 2
Manual position
Using  the  manual  function  the  valve  can  be 
opened by hand.
To open the valve:
Press the cover and turn anticlockwise. The cover 
and bezel  markings  are then  out of  alignment 
(see Picture 3). The valve is now open
To close the valve:
Press and turn the cover clockwise until it clicks. 
The cover and bezel markings are now in align-
ment (see Picture 4)
Valve  Valve
Open  Closed
Picture 3  Picture 4
NOTE: the  TS+  will  only  work  properly  in  the 
closed position (see Picture 4)
468 931 003 497-6
red
position 
indicator
t
This  product  should  not  be  disposed  of  with 
household waste. Please  recycle  the  products 
where facilities for electronic waste exist. Check 
with your local authorities for recycling advice.