Instructions

468 931 014 352
Installation and
Operating Instructions
UTE 2100
UTE 2500
UTE 2500-24
1. Area of use
The UTE 2100 and UTE 2500 electronic tempera-
ture controllers can be used to control the floor
and room temperature.
2. Installation site
The controller should be mounted in a place
in the room that is easy to access for operation.
Mounting height: approx. 1.5 m above the
floor.
Preference should be given to installation
on an internal wall. Avoid external walls and
draughts from windows and doors.
Ensure that the rooms normal convection air
reaches the controller freely without restric-
tion. The controller should therefore not be
mounted inside shelf units or behind curtains
and similar coverings.
Extraneous heat has a negative influence on
the control accuracy.
Direct sunshine, proximity to televisions, radios
and heaters, lamps, stoves and heating pipes
must be avoided.
Install in flush-mounting box 60mm
3. Electrical connection
Important!
Disconnect the electric circuit from the
mains
Connection in the following steps:
• Pull off the temperature control knob
• Undo the fastening screw
• Remove the top part of the housing
Connect as shown on the circuit diagram (see
bottom of housing or circuit diagram in these
instructions.)
Install in the reverse order
Important!
Mount in non-conductive (plastic)
flush-mounting boxes only.
Abbreviations used in the circuit diagram
L = Outer conductor (phase)
N = Neutral conductor (previously Mp)
> = Connection for clock signal for tem-
perature reduction
U = Heating load connection
P = Cooling load connection
H/C> = Connection for heating/cooling input
signal
Red indicator lamp: Controller requests heat
Green indicator lamp: Temperature reduction on
Blue indicator lamp: Cooling mode is active
4. Circuit diagram
UTE 2100
L N
L
N
UTE 2500
L N
L
N
H/C >
UTE 2500-24
AC1 AC2
AC1
AC2
H/C >
Jumper:
The jumpers (links) can be used to set whether
the controller operates “normally closed” (NC) or
“normally open (NO) actuators. Depending on
the setting, the output signal is as follows:
NC: 230 V / 24 V Heat/Cool On
0 V Heat/Cool Off
NO: 230 V / 24 V Heat/Cool Off
0 V Heat/Cool On
6. Dimensions
6.1 55 x 55 version
42
17
55
71
6.2 50 x 50 version
42
17
50
71
Important!
The device may only be opened by an electrically
skilled person and must be installed as shown on
the circuit diagram on the device and in these in-
structions. The existing safety regulations must be
followed.
The relevant installation measures must be taken
to achieve the requirements of protection class II.
This independently mountable electronic device
is used to control the temperature in dry and en-
closed rooms only, with normal environment. This
device conforms to EN 60730, it operates accord-
ing to type 1C action.
5. Technical Data
Order designation UTE 2100 UTE 2500 UTE 2500-24
Voltage supply 230 V AC 50 Hz (207 253 V) 230 V AC 50 Hz (207 253 V) 24 V AC 50 Hz (21.6 V … 26.4 V)
Temperature setting range 5 °C … 30 °C 5 °C … 30 °C 5 °C … 30 °C
Output TRIAC TRIAC TRIAC
Number of switchable
actuators
5
(3 W electrothermal)
5
(3 W electrothermal)
5
(3 W electrothermal)
Continuous switching
current
0 … 65 mA 0 … 65 mA 0 … 65 mA
Inrush current
(short-term for 2 s)
max. 5 A max. 5 A max. 5 A
Control algorithm PWM PWM PWM
PWM cycle time 10 min 10 min 10 min
Temperature reduction* 3.5 °C 3.5 °C
Frost protection 5 °C 5 °C 5 °C
LED display Red:
Heat
Green:
Temp. reduction on
Blue:
Cool
Red:
Heat
Green:
Temp. reduction on
Blue:
Cool
Range restriction Integrated in the control knob
Integrated in the control knob Integrated in the control knob
Ambient temperature 0 … 45 °C 0 … 45 °C 0 … 45 °C
Storage -25 … 60 °C -25 … 60 °C -25 … 60 °C
Overvoltage category III III III
Rated
pulse voltage
4 kV 4 kV 4 kV
Voltage and current for EMC
emission testing purposes
230 V, 0.1 A 230 V, 0.1 A 24 V, 0.1 A
Protection class II II III
Degree of protection IP30 IP30 IP30
Software class Class A Class A Class A
Pollution degree 2 2 2
Temperature for ball inden-
tation test
75 °C 75 °C 75 °C
Weight 36 g 39 g 35.1 g
Energy class
(to EU 811/2013, 812/2013,
813/2013, 814/2013)
IV = 2 % IV = 2 % IV = 2 %
UTE 2500
UTE 2500-24
UTE 2100
*
This product should not be disposed of with
household waste. Please recycle the products
where facilities for electronic waste exist. Check
with your local authorities for recycling advice.
7. Restricting the temperature setting
range:
The temperature controller is set in the factory
to the maximum setting range of 5 30 °C
(see Figure 1).
There are 2 adjusting rings in the control knob.
These can be used to set the temperature set-
ting range as required.
Figure 1:
Restricting the temperature setting range
* in cooling mode the setpoint temperature is increased by 3.5 °C.