Instructions
468 931 004 353
Installation and
Operating Instructions
UTE 2800-R
UTE 2800-F
UTE 2800-L
1. Area of use
The UTE 2800 electronic temperature controllers
can be used for the following applications:
UTE 2800-R can be used to control the room tem-
perature in conjunction with:
• Actuators for underfloor heating and convector
heaters
• Oil or gas-fired hot water heaters
• Circulation pumps / heat pumps
• Electric heaters
UTE 2800-F can be used to control the floor tem-
perature in conjunction with:
• Direct underfloor heating
• Floor heating mat systems
UTE 2800-L can be used for room temperature
control in conjunction with:
• Electrical underfloor heating (if the floor tempe-
rature has to be limited to a maximum value)
• Hot water underfloor heating in conjunction with
electro-thermal actuators.
2. Installation site
• The controller should be mounted in a place in
the room that is easy to access for operation.
• Mounting height: approx. 1.5 m above the floor.
• Preference should be given to installation on an
internal wall. Avoid external walls and draughts
from windows and doors.
• Ensure that the room’s normal convection air
reaches the controller freely without restriction.
The controller should therefore not be mounted
inside shelf units or behind curtains and similar
coverings.
• Extraneous heat has a negative influence on the
control accuracy.
• Direct sunshine, proximity to televisions, radios
and heaters, lamps, stoves and heating pipes
must be avoided.
• Install in flush-mounting box 60mm
3. Elektrischer Anschluss
3. Electrical connection
Important!
Disconnect the electric circuit from the mains
Connection in the following steps:
• Pull off the temperature control knob
• Undo the fastening screw
• Remove the top part of the housing
• Connect as shown on the circuit diagram (see
bottom of housing or circuit diagram in these
instructions.)
• Install in the reverse order
Important!
Mount in non-conductive (plastic)
flush-mounting boxes only.
Connection remote sensor
A remote sensor is required to operate the UTE
2800-F and the UTE 2800-L. This sensor should be
mounted so that the temperature to be controlled
can be registered correctly.
The sensor should be laid in a protective tube. This
makes replacement at a later date easier.
The remote sensor can be extended up to approx.
50 m with a 2-wire cable for 230 V. Avoid close pa-
rallel routing with mains cables, e.g. in the cable
duct.
Important!
The sensor cables carry mains voltage.
Abbreviations used in the circuit diagram
L = Outer conductor (phase)
N = Neutral conductor (previously Mp)
> = Connection for clock signal for tempera-
ture reduction
U = Heating load connection
Red indicator lamp: Controller requests heat
Green indicator lamp: Cooling mode is active
4. Circuit diagram
UTE 2800-R
L
N
N
UTE 2800-F / UTE 2800-L
L
N
N
Sensor
UTE 2800-F UTE 2800-L
6. Dimensions
6.1 Variant 55 x 55
42
17
55
71
6.2 Variant 50 x 50
42
17
50
71
7. Power switch
The power switch is integrated in the rotary knob.
To switch off the device, the rotary knob must be
turned to the off symbol (O). When moving into
this position, a click can be heard and a slight
resistance can be felt. Please note that the frost
protection function is deactivated in this device
status.
Order designation UTE 2800-R UTE 2800-F UTE 2800-L
Voltage supply 230 V AC 50 Hz (207 … 253V) 230 V AC 50 Hz (207 … 253V) 230 V AC 50 Hz (207 … 253V)
Temperature setting range 5 °C … 30°C 10 °C … 40 °C 5 °C … 30 °C
Output Relay, normally open
(NO relay)
Relay, normally open
(NO relay)
Relay, normally open
(NO relay)
Switching current 16 (4) A 16 (4) A 16 (4) A
Control algorithm PWM – default
2-point (On/Off), adjustable
PWM – default
2-point (On/Off), adjustable
PWM – default
2-point (On/Off), adjustable
PWM cycle time 10 min – default
5 / 20 min - adjustable
10 min – default
5 / 20 min - adjustable
10 min – default
5 / 20 min - adjustable
Hysteresis Adjustable for 2-point
Control algorithm:
0.1 °C or 0.5 °C
Adjustable for 2-point
Control algorithm:
0.1 °C or 0.5 °C
Adjustable for 2-point
Control algorithm:
0.1 °C or 0.5 °C
Temperature reduction 3.5 °C – default
6 °C / 9 °C – adjustable
3.5 °C – default
6 °C / 9 °C – adjustable
3.5 °C – default
6 °C / 9 °C – adjustable
Frost protection 5 °C 10 °C 5 °C
Remote Sensor F 193 720, Length 4 m,
Max. extension: 50 m
F 193 720, Length 4 m,
Max. extension: 50 m
LED display
Red
: Heat
Green:
Temp. reduction
on
Red
: Heat
Green:
Temp. reduction
on
Red
: Heat
Green:
Temp. reduction
on
Range restriction Integrated in the control knob Integrated in the control knob Integrated in the control knob
Ambient temperature 0 … 40 °C 0 … 40 °C 0 … 40 °C
Storage –25 … 60 °C –25 … 60 °C –25 … 60 °C
Overvoltage category III III III
Rated
pulse voltage
4kV 4kV 4kV
Voltage and current for EMC
emission testing purposes
230 V, 0.1A 230 V, 0.1A 230 V, 0.1A
Protection class II II II
Degree of protection IP30 IP30 IP30
Software class Class A Class A Class A
Pollution degree 2 2 2
Temperature for
ball indentation test
75°C 75°C 75°C
Weight 62.2 g 62.2 g 62.2 g
Energy class
(to EU 811/2013, 812/2013,
813/2013, 814/2013)
IV = 2 % IV = 2 % IV = 2 %
8. Restricting the
temperature setting:
The temperature controller is set in the factory
to the maximum setting range of 5 … 30 °C
(see Figure 1).
There are 2 adjusting rings in the control knob.
These can be used to set the temperature setting
range as required.
Figure 1:
Restricting the temperature setting range
9. Resistance table for remote sensor
F 193 720
Temperature Resistance Temperature Resistance
10 °C 66.8 kΩ 30 °C 26.3 kΩ
20 °C 41.3 kΩ 40 °C 17.0 kΩ
25 °C 33 kΩ 50 °C 11.3 kΩ
Important!
The device may only be opened by an electrically
skilled person and must be installed as shown on
the circuit diagram on the device and in these in-
structions. The existing safety regulations must be
followed.
The relevant installation measures must be taken
to achieve the requirements of protection class II.
This independently mountable electronic device
is used to control the temperature in dry and en-
closed rooms only, with normal environment. This
device conforms to EN 60730, it operates accord-
ing to type 1C action.
5. Technical Data
*
This product should not be disposed of with
household waste. Please recycle the products
where facilities for electronic waste exist. Check
with your local authorities for recycling advice.
19.04.2021 Typ 547 81x xxxxx. Z.- Nr. 007 63 3055 4xx
Datei-Nr: 7Li10140.pdf
10140
6
5
3
2