Specifications
TM9-2330-384-14&P
2-18. GENERALFUELHANDLINGREQUIREMENTS(Con't).
q. When bottom or top loading, keep emergency valve CLOSED.
r. When bottom loading or unloading, keep vapor vent OPEN.
s. When bottom loading, activate the precheck cycle to check for proper operation of automatic
shut-off (jet level sensor) circuit (see paragraph 2-19).
t.
If a malfunction in automatic shut-off (jet level sensor) circuit causes semitrailer to not bottom
load, automatic shut-off circuit can be bypassed and semitrailer manually bottom loaded by:
(1) pulling emergency valve control lever to open emergency valve (see paragraph 2-2), and
(2) positioning observer at manhole opening to alert fuel handler when tank is to capacity.
When mission is complete, notify unit maintenance to troubleshoot the malfunction.
u. Make sure hazardous materials placards reflect the grade of the fuel being hauled in the
semitrailer.
2-19. BOTTOM LOADING (PREFERRED METHOD).
a. TO BOTTOM LOAD AT REAR INLET.
WARNING
DO NOTsmoke while loading or unloading fuel, when handling fuel containers,
or when located within 50 ft. (15.3 m) of fueling or fuel storage areas. Failure
to follow this warning may cause a fire and explosion, resulting in serious
injury or death to personnel.
(1)
Shut down tractor engine and set tractor and semitrailer parking/emergency brakes (see
TM 9-2320-273-10 or TM 9-2320-283-10).
(2)
Remove fire extinguishers from mounting brackets and take to point of operation.
(3)
Open cabinet door. Secure door in open position with door prop.
WARNING
Connect bonding and grounding connection before beginning any fuel handling
operation. Maintain bonding and grounding connection until after fuel handling
is completed. DO NOT connect semitrailer grounding cable to semitrailer
grounding stud. Connections must be made to clean, unpainted surfaces. An
unbonded or ungrounded or improperly bonded and grounded semitrailer
could produce a spark. The resulting explosion will cause serious injury or
death to personnel.
(4)
Connect bonding and grounding connection (see paragraph 2-17).
Change1