Specifications
TM 9-2330-384-14&P
2-20. TOPLOADING(ALTERNATIVEMETHOD)(Con't).
b. Remove fire extinguishers from mounting brackets and take to point of operation.
c. Open cabinet door. Secure door in open position with door prop.
WARNING
Connect bonding and grounding connection before beginning any fuel handling
operation. Maintain bonding and grounding connection until after all fuel
handling is completed. DO NOT connect semitrailer grounding cable to
semitrailer grounding stud. Connections must be made to clean, unpainted
surfaces. An unbonded and ungrounded or improperly bonded and grounded
semitrailer could produce a spark. The resulting explosion will cause injury
or death to personnel.
d. Connect bonding and grounding connection (see paragraph 2-17).
e. If loading hose will not reach manhole (1), connect transfer hoses stowed in curbside stowage
tubes, as required.
2
3
2-46