Drawing : - TPC427 Issue :-2 Date : - 26/08/15 RM4500 INDUSTRIAL DEHUMIDIFIER OWNER’S MANUAL www.eipl.co.
Drawing : - TPC427 Issue :-2 Date : - 26/08/15 RM4500 PACKAGE CONTENTS Item Description Quantity 10570RG-US Dehumidifier 1 3086144 Quick release hose coupling 1 3944110 PVC Tube – 3/8” I/D 7.
Drawing : - TPC427 Issue :-2 Date : - 26/08/15 INTRODUCTION Designed for a wide range of applications, the RM4500 is a rugged, industrial unit, which utilizes an energy-efficient compressor and a compact portable design to provide easy efficient drying.
Drawing : - TPC427 Issue :-2 Date : - 26/08/15 SPECIFICATIONS MODEL: 10570RG-US HEIGHT: 44” (1115mm) WIDTH: 25” (625mm) DEPTH: 28” (710mm) WEIGHT: 170 lbs (77 Kg) AIRFLOW: 350 CFM (600 M3/hr) POWER SUPPLY: 110V/ 60Hz/ 1 ph FINISH: Rotational Moulded polyethylene OPERATING RANGE: 33°F – 95°F REFRIGERANT: R-407c (22.9 oz) "This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed.
Drawing : - TPC427 Issue :-2 Date : - 26/08/15 OPERATION The following procedures should be followed to test the RM4500 for correct operation: 1. After unpacking, examine all external features to confirm damagefree shipment. Report all defects and damage at once. Connect the power cable to a grounded 15 Amp electrical outlet. 2. Check dehumidification process as follows: CAUTION: DO NOT REMOVE COVERS WHEN UNIT IS IN OPERATION A. B. C. D. E. Place unit on a level surface.
Drawing : - TPC427 Issue :-2 Date : - 26/08/15 ROUTINE MAINTENANCE WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE MAINTNENANCE ON ITEMS 1, 2, 3, 4 & 5 To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows: 1. Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air.
Drawing : - TPC427 Issue :-2 Date : - 26/08/15 REPAIRS 1. Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part. 2. If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action. Any competent refrigeration technician will be able to service the equipment. The following procedure must be used: a.
Drawing : - TPC427 Issue :-2 Date : - 26/08/15 TROUBLESHOOTING SYMPTOM CAUSE Unit inoperative 1. No power to unit Little or no airflow 1. Fan motor burnt out 2. Dirty refrigeration coils 3. Loose electrical wiring Little or no water extraction 1. Insufficient air flow 2. Compressor fault 3. Loss of refrigerant gas Little or no defrost when required 1. Faulty timer 2. Faulty reversing valve Unit vibrates excessively 1. Loose compressor 2. Damaged fan Water flooding inside the machine 1.
Drawing : - TPC427 Issue :-2 Date : - 26/08/15 RM4500 SPARE PARTS LIST NUMBER 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 DESCRIPTION Timer Condenser coil Evaporator coil Filter Capillary Solenoid valve Filter dryer Compressor Solenoid coil Hour meter Run capacitor On/Off switch Power Relay Pump purge switch Fan Fan inlet ring Duct attachment Grille Wheel Condensate pump Heat Exchanger Page 9 of 12 PART NUMBER 1619508 2057025 2057024 2057031 3014249 3020833 3020957 3944938 3030453 3030779 303
Drawing : - TPC427 Issue :-2 Date : - 26/08/15 Page 10 of 12
Drawing : - TPC427 Issue :-2 Date : - 26/08/15 Page 11 of 12
Drawing : - TPC427 Issue :-2 Date : - 26/08/15 UK Head Office American Sales Office German Sales Office Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News Virginia, 23606-2575 USA Ebac Industrial Products Ltd. Gartenfelder Str.