Installation Guide

Page 4 of 13
Drawing : - TPC 400
Issue : -1
Date : -21/02/13
SPECIFICATIONS
M
ODEL
:
DD700
H
EIGHT
:
1020mm (40”)
W
IDTH
:
711mm (28”)
D
EPTH
:
584mm (23”)
W
EIGHT
:
TBC
P
OWER
S
UPPLY
:
220V, 3 ph, 60Hz
P
OWER
7.5 kW (max)
P
ROCESS
A
IRFLOW
M
AXIMUM
:
1500m3/hr (883 cfm)
P
ROCESS
A
IRFLOW
N
OMINAL
:
700m3/hr (412 cfm)
R
EGENERATION
A
IRFLOW
N
OMINAL
:
160m3/hr (94 cfm)
P
ROCESS
A
IR
O
UTLET
D
IA
:
200mm (8”)
R
EGENERATION
A
IR
O
UTLET
D
IA
:
150mm (6”)
R
OTOR
W
HEEL
S
PEED
:
13.6
R
OTOR
S
IZE
D
IA X
D
EPTH
:
350mm (13.8”) x 100mm (4”)
H
IGH
E
XTRACTION
S
ETTING
@
27°C
60%
RH:
109 l/day (231 ppd)
H
IGH
E
FFICIENCY
S
ETTING
@
27°C
60%
RH:
87 l/day (184 ppd)
D
EEP
D
RYING SETTING
@
27°C
60%
RH:
97 l/day (205 ppd)
T
YPICAL
D
RY
A
IR
O
FF
H
IGH
E
XTRACTION
S
ETTING
(%RH)
18
T
YPICAL
D
RY
A
IR
O
FF
H
IGH
E
FFICIENCY
S
ETTING
(%RH)
18
T
YPICAL
D
RY
A
IR
O
FF
D
EEP
D
RYING
S
ETTING
(%RH)
8
M
INIMUM
O
PERATING
T
EMPERATURE
:
-20°C (-4°F)
M
AXIMUM
O
PERATING
T
EMPERATURE
40°C (104°F)