Datasheet

03/20/2012 HPL-ED2011 V2.0 EN (UX111) 3 / 5
Safe isolation to VDE 0106 Part 101 and Part 101/A1
between the auxiliary contacts V
AC
300
Conventional thermal current I
th
A 6
Rated operational current I
e
A
AC-15
Make contact
120 V I
e
A 1.5
240 V I
e
A 1.5
415 V I
e
A 0.5
500 V I
e
A 0.3
Break contact
120 V I
e
A 1.5
240 V I
e
A 1.5
415 V I
e
A 0.7
500 V I
e
A 0.5
DC-13 L/R - 15 ms
24 V I
e
A 0.9
60 V I
e
A 0.75
110 V I
e
A 0.4
220 V I
e
A 0.2
Short-circuit rating without welding
max. fuse A
gG/
gL
4
Notes
Notes�Ambient temperature: operating range to IEC/EN 60947, PTB: -5°C to +50°C
Rated operational current: Making and breaking conditions to DC-13, L/R constant as stated
See overlay: “Fuses” for short-circuit rating time/current characteristic (please enquire)
Technical�data�according�to�ETIM�4.0
Number of auxiliary contacts as N/Cs 1
Number of auxiliary contacts as N/Os 1
Mounting type Direct mounting
Adjustable current range A 9
Connection type main circuit Screw connection
Tripping class CLASS 10
Number of auxiliary contacts as changeover contacts 0
Characteristics