Cut Sheet

03/19/2014 HPL-ED2014 V2.13 EN 4 / 12
415 V
I
e
A 65
440V
I
e
A 65
500 V
I
e
A 65
660 V 690 V
I
e
A 37
Motor rating
P kWh
220 V 230 V
P kW 20
240V
P kW 22
380 V 400 V
P kW 30
415 V
P kW 39
440 V
P kW 41
500 V
P kW 47
660 V 690 V
P kW 35
AC-4
Open, 3-pole: 50 –60 Hz
220 V 230 V
I
e
A 25
240 V
I
e
A 25
380 V 400 V
I
e
A 25
415 V
I
e
A 25
440 V
I
e
A 25
500 V
I
e
A 25
660 V 690 V
I
e
A 20
Motor rating
P kWh
220 V 230 V
P kW 7
240 V
P kW 7.5
380 V 400 V
P kW 12
415 V
P kW 13
440 V
P kW 14
500 V
P kW 16
660 V 690 V
P kW 17
DC
Rated operational current, open
DC-1
60 V
I
e
A 72
110 V
I
e
A 72
220 V
I
e
A 65
440 V
I
e
A 2.9
DC-3
60 V
I
e
A 72
110 V
I
e
A 72
220 V
I
e
A 35
440 V
I
e
A 0.6
DC-5
60 V
I
e
A 72
110 V
I
e
A 72
220 V
I
e
A 35
440 V
I
e
A 0.6
Current�heat�loss
3-pole at I
th
W 28.8
Current heat loss at I
e
to AC-3/400 V
W 19
Impedance per pole
mΩ 1.5
Magnet�systems
Voltage tolerance
x U
c
AC operated
Pick-up x U
c
0.8 - 1.1
Drop-out voltage AC operated
Drop-out x U
c
0.3 - 0.6