03/19/2014 HPL-ED2014 V2.13 EN 2 / 12
Ambient temperature
°C
Open
°C - 25 - 60
Enclosed
°C - 25 - 40
Storage
°C - 40 - 80
Mounting position, AC- and DC operated
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact
g 10
Auxiliary contacts
N/O contact
g 7
N/C contact
g 5
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-
mounted
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact
g 10
Auxiliary contacts
N/O contact
g 7
N/C contact
g 5
Protection type
IP00
Protection against direct contact when actuated from front (EN 50274)
Finger and back-of-hand proof
Weight
AC operated
kg 0.9
DC operated
kg 1.1
Terminal capacity main cable
Solid
mm
2
1 x (0.75 - 16)
2 x (0.75 - 16)
Flexible with ferrule
mm
2
1 x (0.75 - 35)
2 x (0.75 - 25)
Stranded
mm
2
1 x (16 - 50)
2 x (16 - 35)
Solid or stranded
AWG 12 - 2
Flat conductor
Lamellenzahl
x Breite x
Dicke
mm 2 x (6 x 9 x 0.8)
Main cable connection screw/bolt
M6
Tightening torque
Nm 3.3
Terminal capacity control circuit cables
Solid
mm
2
1 x (0.75 - 4)
2 x (0.75 - 4)
Flexible with ferrule
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Solid or stranded
AWG 18 - 14
Control circuit cable connection screw/bolt
M3.5
Tightening torque
Nm 1.2
Tool
Main cable
Pozidriv screwdriver
Size 2
Standard screwdriver
mm 0.8 x 5.5
1 x 6
Control circuit cables
Pozidriv screwdriver
Size 2
Standard screwdriver
mm 0.8 x 5.5
1 x 6
Terminal capacity control circuit cables
Solid
mm
2
1 x (0.75 - 2.5)