Installation Manual
Appendix B
50 H-Max Series Variable Frequency Drive MN04008005E—May 2017 www.eaton.com
Table 25. International Cable and Fuse Sizes 380–480 Vac Ratings
Note:
1. If power cubes are used, a UL recognized Type T fuse is recommended.
2. Based on maximum environment of 104°F (40°C).
3. If bypass is used, a UL recognized Type T fuse is recommended
Frame
Amp
Suffix
VFD
I(L)
Amps
at
40° C
VFD
I(L)
Amps
at
50° C
[kW]
400V
at
50 Hz
Fuse
Rating
(gG/gL)
Mains and
Motor
Cable
Cu (mm
2
)
Terminal
Cable Size
Main
Terminal
Cu (mm
2
)
Earth
Terminal
Cu (mm
2
)
FS4 3D4 3.4 2.6 1.1 6 3*1.5+1.5 1–6 solid or
1–4 stranded
1–6
4D8 4.8 3.4 1.5 6 3*1.5+1.5 1–6 solid or
1–4 stranded
1–6
5D6 5.6 4.3 2.2 10 3*1.5+1.53 1–6 solid or
1–4 stranded
1–6
8D0 8.0 5.6 3.0 16 3*2.5+2.5 1–6 solid or
1–4 stranded
1–6
9D6 9.6 8 4 16 3*2.5+2.5 1–6 solid or
1–4 stranded
1–6
012 16 12 7.5 16 3*2.5+2.5 1–6 solid or
1–4 stranded
1–6
FS5 016 23 16 11 20 3*6+6 1–10 1–10
023 31 23 15 25 3*6+6 1–10 1–10
031 38 31 18.5 32 3*10+10 1–10 1–10
FS6 038 46 38 22 40 3*10+10 2.5–50 2.5–35
046 61 46 30 50 3*16+16 2.5–50 2.5–35
061 72 61 37 63 3*25+16 2.5–50 2.5–35
FS7 072 87 72 45 80 3*35+16 6–70 6–70
087 105 87 55 100 3*35+16 6–70 6–70
105 140 105 75 125 3*50+25 6–70 6–70
FS8 140 170 140 90 160 3*70+35 35–185 6–70
170 205 170 110 200 3*95+50 35–185 6–70
205 261 205 132 250 3*120+70 35–185 6–70
FS9 261 310 251 160 315 3*185+95 35–185 6–95
310 3.4 2.6 1.1 350 2*3*95+50 35–185 6–95