Installation Manual

Installation Requirements
36 H-Max Series Variable Frequency Drive MN04008005E—May 2017 www.eaton.com
Table 17. International EMC Protection Cable Requirements
Figure 26. Cable Description
Note
1
360° earthing of the shield with cable glands in motor end needed for EMC Level C2.
1st Environment 2nd Environment EMC Levels According to EN61800-3 (2004)
Cable Type Category C2 Category C3 Level T
Line voltage/mains 1 1 1
Motor cable 3
1
22
Control cable 4 4 4
Cable Categories
Cable Category
Description
(All cables are rated for the specific operating voltage)
Recommended
Cable Types
1 Intended for fixed installation MCMK or similar
2 Symmetrical power cable equipped with a concentric protection wire. MCMK or similar
3 Symmetrical power cable with compact low-impedance shield.
Recommended cable transfer impedance of 1–30 Mhz max. See figure below.
MCCMK, EMCMK,
or similar
4 Screened cable equipped with compact low-impedance shield JAMAK, SAB/
ÖCuY
23
-0 or similar
PE Conductor
and Shield
PE Conductor
Shield