Data Sheet

DATASHEET - XIOC-NET-DP-M
Communication module for XC100/200, 24 V DC, PROFIBUS-DP master
Part no. XIOC-NET-DP-M
Catalog No. 257908
EL-Nummer
(Norway)
4519683
Delivery program
Function Communication modules
Compact I/O system for connection to XC100/200 Modular PLCs
XC100/200 expandable with up to 15 XI/OC modules
Optionally, screw terminals or spring-loaded terminals for digital/analog modules
Description PROFIBUS-DP master module
Technical data
General
Standards IEC/EN 61131-2
EN 50178
Ambient temperature °C 0 - +55
Storage ϑ °C -20 - +70
Vibration resistance 10 - 57 Hz ±0.075 mm
57 - 150 Hz ±1.0 mm
Mechanical shock resistance g 15
Shock duration 11 ms
Impact resistance 500 g/⌀ 50 mm ±25 g
Overvoltage category/pollution degree II/2
Protection class 1
Degree of Protection IP20
Emitted interference DIN/EN 55011/22, Class A
Weight kg 0.2
Power supply
Rated voltage U
e
V DC 24 (12)
Admissible range 20.4 – 28.8 (11.8 – 14.4)
Residual ripple % ≦ 5
Neutral poles
Duration of dip ms 10
Repetition rate s 1
Supply voltage 5 V DC ±5 %
Maximum power loss P
v
W 7.2
Interfaces
Built-in interfaces PROFIBUS DP, RS485, EN 50170
Protocol PROFIBUS-DP master (class 1)
Data transfer rate kBit/s 9.6 to 12000
Function PROFIBUS-DP interface
Master (Class 1)
Potential isolation Yes
Number of slaves 124
Transmit/receive data 3 500 Byte each
Bus terminating resistors Switchable
Inputs/outputs Max. 244 Bytes per slave
Plug arrangement 9-pole SUB-D socket connector
Current consumption I
e
mA 300
Baud rate/length kBd 9.6 KBit/s with 1200 m
19.2 KBit/s with 1200 m
93.75 KBit/s with 1200 m
187.5 KBit/s with 1000 m
500 KBit/s with 400 m
1500 KBit/s with 200 m
06/16/2021 Eaton 257908 ED2021 V80.0 EN 1 / 4