Data Sheet
DATASHEET - XIOC-NET-DP-M
Communication module for XC100/200, 24 V DC, PROFIBUS-DP master
Part no. XIOC-NET-DP-M
Catalog No. 257908
EL-Nummer
(Norway)
4519683
Delivery program
Function   Communication modules
   Compact I/O system for connection to XC100/200 Modular PLCs
XC100/200 expandable with up to 15 XI/OC modules
Optionally, screw terminals or spring-loaded terminals for digital/analog modules
Description   PROFIBUS-DP master module
Technical data
General
Standards   IEC/EN 61131-2
EN 50178
Ambient temperature  °C 0 - +55
Storage ϑ °C -20 - +70
Vibration resistance   10 - 57 Hz ±0.075 mm
57 - 150 Hz ±1.0 mm
Mechanical shock resistance  g 15
Shock duration 11 ms
Impact resistance   500 g/⌀ 50 mm ±25 g
Overvoltage category/pollution degree   II/2
Protection class   1
Degree of Protection   IP20
Emitted interference   DIN/EN 55011/22, Class A
Weight  kg 0.2
Power supply
Rated voltage U
e
V DC 24 (12)
Admissible range   20.4 – 28.8 (11.8 – 14.4)
Residual ripple  % ≦ 5
Neutral poles   
Duration of dip  ms 10
Repetition rate  s 1
Supply voltage   5 V DC ±5 %
Maximum power loss P
v
W 7.2
Interfaces
Built-in interfaces   PROFIBUS DP, RS485, EN 50170
Protocol   PROFIBUS-DP master (class 1)
Data transfer rate  kBit/s 9.6 to 12000
Function   PROFIBUS-DP interface
Master (Class 1)
Potential isolation   Yes
Number of slaves   124
Transmit/receive data   3 500 Byte each
Bus terminating resistors   Switchable
Inputs/outputs   Max. 244 Bytes per slave
Plug arrangement   9-pole SUB-D socket connector
Current consumption I
e
mA 300
Baud rate/length  kBd 9.6 KBit/s with 1200 m
19.2 KBit/s with 1200 m
93.75 KBit/s with 1200 m
187.5 KBit/s with 1000 m
500 KBit/s with 400 m
1500 KBit/s with 200 m
06/16/2021 Eaton 257908 ED2021 V80.0 EN 1 / 4