Specifications
Industrial ePDUs
EATON CORPORATION Enclosure Power Distribution Units
36
Cable Assembly Options:
CBL113: 10/5 cable 9’ long terminated with a NEMA L21-30P at one end and a mating IEC309 connector at the other end.
For use in North America at 120/208V~
CBL114: 5x4.0 mm harmonized cable 9’ long with an IEC309 connector at both ends. For use in Europe at 230/400V~
This system is designed to be controlled locally or remotely via a remote control panel (refer to pages 38-39).
International PC2672 series three-phase systems
120/208V~ OR 230V/400V~, Three-Phase WYE, 30A, 50/60 Hz
EMI/RFI filtering
• Common mode - line to ground
• Differential mode - line to line
• Refer to Chart 9 on page 40
(3) Indicator lights
• Power on to PH-X, -Y, -Z
(4) Remote I/O ports
• Two front / Two rear: one on each side is sequence and the
other is for remote on/off and EPO control. The PC2672 is
controlled remotely only
• Latching remote - (N/C) EPO between pins 2 & 3, momentary
start between pins 1 & 3
Voltage Selectable
Catalog Number
Full Load
Per Phase
Circuit
Breaker
Secondary Listed
Breakers, (1) Each
For The C19 Outlets
Secondary Listed
Breakers, (1) Each For
A Pair of C13 Outlets
Receptacles
EMI/RFI
Filter
Cord (ft)
Dimensions
(H x W x D, in)
PC2672
2880 VA
at 120/208V or
5520 VA
at 230/400V
(3) 30A (4) 16A (6) 10A
(12) C13
(4) C19
(1) IEC309 32A
30A 5 5.2 x 19.0 x 16.5
Front view Rear view