Industrial ePDUs
Intelligent Power Control IPC3600 Series
(12) Indicator lights
• Main power system on
• Power on to outlets 1-8
• Two data and ethernet link
EMI/RFI filtering
• Common mode - line to ground
• Differential mode -line to line
• Filtered inlet isolates noise before entering the system
• Refer to chart 4 on page 40
Spike/surge suppression
• Line to neutral (or line)
• Refer to chart 1 on page 40
Serial/ethernet
• Serial RS232 via RJ22 connector on the rear. 6’ RJ22 to DB9
cable included
• Serial baud rate is 9600 default or 38,400 maximum
• Ethernet (10/100) network via RJ45 connector on the rear. 6’
network cable included
• Network setup allows DHCP or any static public/private IP
address
Software interfaces
• Web interface provides a graphic control interface through a
Web browser
• Telnet interface provides a text menu control interface with any
terminal emulation software
• SNMP allows read/write capability with trapping
• Email notication system provides email alerts or logs showing
user activity
• Serial interface provides a text menu control interface with any
terminal emulation software
• FTP utility allows rmware upgrades
Software security
• User name/password security
• Settings allow the administrator to disable unused interfaces
Software features
• Administrator and multiple users can be congured
• User level access can be limited to specic outlets
• Unit and outlet names can be congured
• Outlet groups can be created to perform an action on multiple
outlets
• Outlet control includes individual, group and all outlet global
control
• Outlet actions include on or off and reboot
• Global sequence allows all the outlets to be turned on or off in
a preset sequence up to 999 seconds
• Outlet reboot automatically turns an outlet off and back on with
one command at a preset time up to 999 seconds
• Email notication allows up to two email addresses to receive
notifications of alerts or events
Auto-event scheduling
Administrator can configure on or off events for outlets or groups.
The event occurs at the preset time daily or weekly.
IPC36XX
Front view
Rear view
IPC3601
Rear view
IPC3602
Catalog Number Full Load
Ethernet/
Serial
Receptacles
Circuit
Breaker
EMI/RFI
Filter
Surge
Suppression
Input
Plug
Cord (ft)
Dimensions
(H x W x D, in)
IPC3601
1920 VA @ 120V~
3840 VA @ 240V~
Yes (8) C13 (1) 20A 20A Yes C20 Inlet
Not
Included
1.7 x 19.0 x 19.5
IPC3602
1920 VA Yes (8) 5-15R (1) 20A 20A Yes C20 Inlet
Not
Included
1.7 x 19.0 x 19.5
IPC3601-F3-3316
5760 VA Yes (8) C13 (2) 15A No Yes L6-30P 10 1.7 x 19.0 x 19.5