Specifications

EATON CORPORATION Enclosure Power Distribution Units
22
Managed ePDUs
Managed ePDUs
Eaton Managed ePDUs allow you to monitor and control critical factors such as voltage, current and power factor down to the
individual outlet.
Catalog Number
Outlet Level
Monitoring
Outlet Level
Switching Input Plug
1
Breakers Max kW Orientation Receptacles
Dimensions
(H x W x D, in)
eMA012
3 3
L6-20P
2
None 3.3 0U (20) C13, (4) C19 60.0 x 2.2 x 2.6
eMA006
3 3
L21-20P None 5.8 0U (21) C13, (3) C19 60.0 x 2.2 x 2.6
eMA010
3 3
L6-30P (2) 20A 5.8 0U (20) C13, (4) C19 68.0 x 2.2 x 2.6
eMA011
3 3
L21-30P (3) 20A 8.6 0U (21) C13, (3) C19 68.0 x 2.2 x 2.6
eMA013
3 3
IEC 309-516P6W None 11.5 0U (12) C13, (12) C19 68.0 x 2.2 x 2.6
eMA007
3 3
CS8365 (3) 20A 12.6 0U (21) C13, (3) C19 68.0 x 2.2 x 2.6
eMA009
3 3
IEC 309-460P9W (6) 20A 17.3 0U (12) C13, (12) C19 72.4 x 2.2 x 2.6
eMA014
3 3
IEC 309-532P6W (6) 20A 17.3 0U (12) C13, (12) C19 72.4 x 2.2 x 2.6
1. 10-ft cord length, all units
2. Detachable cordset, C20 cord is also included; 120V cords are optional. Please see accessories.
400V
400V
Key technology features
• Outlet-level monitoring
Outlet-level power switching (on/off/reboot)
• High accuracy monitoring
• Advanced LCD display
• Flexible mounting
• Color-coded section labeling
Optional sensors
EMP001
Environmental Monitoring
Probe for Advanced
Monitored and Managed
ePDUs