Datasheet
03/02/2011 HPL-ED2009 V1.0 EN (UX111) 3 / 5
Contacts Quantity 3
240 V
Rated operational current I
e
A 5
Contacts Quantity 5
DC-13, Control switches L/R = 50 ms
Rated operational current I
e
A 10
Voltage per contact pair in series V 32
Control circuit reliability at 24 V DC, 10 mA Fault probability H
F
< 10
-5
, < 1 fault in 100000 operations
Notes
Notes�For mechanical shock resistance: T3.../I... >12g
Applies to T0(3).../SVB: isolating characteristics to IEC/EN 60947 Ufor rated operational voltage up to 500 V AC
Applies to rated uninterrupted current I
u
of the contact: with T5‐4‐8344/I5 max. 95 A
For terminal capacity solid, stranded and flexible:
T0(3), (6), (8)...: Maximum of 2 cross-section sizes difference admissible between 2 conductors
T5(B)-...: Maximum of 1 cross-section size difference admissible between 2 conductors
For type T8‐3‐8342/... the following applies: switching angle = 90° and flat connection = 1 busbar 25 × 5 or 2 busbars 20 × 3
For utilisation category AC-4 (extreme load: 100 % inching, reversing or plugging)
The blocked rotor current of the motor should not exceed the rated current of the switch for AC-21A to ensure a reasonable device lifespan.
Dimensions
not included