Datasheet

03/02/2011 HPL-ED2009 V1.0 EN (UX111) 2 / 5
AB 60 % DF × I
e
1.3
Short-circuit rating
Fuse A gG/gL 20
Rated short-time withstand current (1 s current) I
cw
A
rms
320
Safe isolation to VDE 0106 Part 101 and Part 101/A1
between the contacts V AC 440
Switching angles ° 90
60
45
30
Contact units 11
Double-break contacts max. 22
Current heat loss per contact at I
e
W 0.6
Terminal�capacities
Solid or stranded
mm
2
1 × (1 – 2.5)
2 × (1 – 2.5)
Flexible with ferrule to DIN 46228
mm
2
1 × (0.75 – 1.5)
2 × (0.75 – 1.5)
Terminal screw M3.5
Tightening torque Nm 1
Switching�capacity
AC × U
s
Rated making capacity cos ϕ = 0.35 A 130
Rated breaking capacity, motor load switch cos ϕ = 0.35 A
230 V A 100
400 V A 110
500 V A 80
690 V A 60
Rated operational current 440 V load-break switch AC-21A I
e
A 20
AC-23A Motor load switches (main switches maintenance switches) P kW
230 V P kW 3.5
400 V P kW 6.5
500 V P kW 13
Rated operational current control switch AC-15
230 V I
e
A 6
400 V I
e
A 4
500 V I
e
A 2
DC × U
s
DC-1, Load-break switches L/R = 1 ms
Rated operational current I
e
A 10
Voltage per contact pair in series V 60
DC-21A I
e
A
Rated operational current 240 V I
e
A 1
240 V Contacts Quantity 1
DC-23A, motor load switch L/R = 15 ms
24 V
Rated operational current I
e
A 10
Contacts Quantity 1
48 V
Rated operational current I
e
A 10
Contacts Quantity 2
60 V
Rated operational current I
e
A 10
Contacts Quantity 3
120 V
Rated operational current I
e
A 5