Installation Manual

Technical Data
60 9000X AF Drives MN04001004E—May 2011 www.eaton.com
SVX9000/SPX9000 Drive Specifications, continued
Description Specification
Environment, continued
Vibration EN 50178, EN 60068-2-6
5 to 50 Hz, displacement amplitude 1 mm (peak) at 3 to 15.8 Hz,
max. acceleration amplitude 1G at 15.8 to 150 Hz
Shock EN 50178, EN 60068-2-27
UPS drop test (for applicable UPS weights)
Storage and shipping: max. 15G, 11 ms (in package)
Enclosure class NEMA 1/IP21 available all ratings
NEMA 12/IP54 available all ratings
Standards
EMC (at default settings) Immunity: Fulfils all EMC immunity requirements
Emissions: EN 61800-3
Safety UL 508C
Product IEC 61800-2
Control Connections
Analog input voltage 0 to 10 Vdc, R–200k ohms differential (–10 to 10 Vdc joystick control)
Resolution 0.1%; accuracy ±1%
Analog input current 0(4) to 20 mA; R
i
–250 ohms differential
Digital inputs (6) Positive or negative logic; 18 to 24 Vdc
Auxiliary voltage +24V ±15%, max. 250 mA
Output reference voltage +10V +3%, max. load 10 mA
Analog output 0(4) to 20 mA; R
L
max. 500 ohms
Resolution 10 bit
Accuracy ±2% or 0 to 10 Vdc, R
L
1k ohms, select with jumper
Digital output Open collector output, 50 mA/48V
Relay output 3 programmable change-over relay outputs
Switching capacity: 24 Vdc/8A, 250 Vac/8A, 125 Vdc/0.4A
Minimum switching load: 5V/10 mA
Continuous capacity: <2 A
rms
Protections
Overcurrent protection Yes
Undervoltage protection Yes
Ground (earth) fault In case of a ground fault in the motor or motor cables, only the
SVX9000/SPX9000 is protected
Input phase supervision Trips if any of the input phases are missing
Motor phase supervision Trips if any of the output phases are missing
Overtemperature protection Yes
Motor overload protection Yes
Motor stall protection Yes
Motor underload protection Yes
Short circuit protection of the +24V
and +10V reference voltages
Yes