Installation Manual
Menu Information
44 9000X AF Drives MN04001004E—May 2011 www.eaton.com
Monitoring Menu (M7)
The Monitoring Menu items are meant for viewing
parameter values during operation. Monitored values are
updated every 0.3 second Monitored items are identified by
item numbers V7.1 to V1.xx, where “xx” varies by
application. The table below provides an example of the
monitored values for the Standard application.
Monitored parameters are not editable from this menu
(see Parameter Menu [M1] to change parameter values).
Monitoring Menu Items—Standard Application Example
Digital Inputs—
DIN1, DIN2, DIN3 Status
Digital Inputs—
DIN4, DIN5, DIN6 Status
Digital and Relay Outputs—
DO1, RO1, RO2 Status
Multimonitor (V7.17)
This parameter allows the viewing and selection (if allowed
by system menu item, P5.5.4) of three simultaneously
monitored items from the Monitored Menu Items shown in
the table above. Use the right arrow key to select the item to
be modified and then the up or down arrow keys to select
the new item. Press the ENTER key to accept the change.
Code Signal Name Unit Description
V7.1 Output frequency Hz Output frequency
V7.2 Frequency reference Hz Frequency reference setting
V7.3 Motor speed rpm Calculated motor speed
V7.4 Motor current A Measured motor current
V7.5 Motor torque % Calculated torque based on nominal motor torque
V7.6 Motor power % Calculated power based on nominal motor power
V7.7 Motor voltage V Calculated motor voltage
V7.8 DC bus voltage V Measured DC bus voltage
V7.9 Unit temperature °C Heatsink temperature
V7.10 Calculated motor
temperature
°C Calculated motor temperature based on the motor nameplate
information and the calculated motor load
V7.11 Analog Input 1 V Voltage input at terminals AI1+ and GND
V7.12 Analog Input 2 mA Current input at terminals AI2+ and AI2–
V7.13 DIN1, DIN2, DIN3 — Digital input status (see figure below)
V7.14 DIN4, DIN5, DIN6 — Digital input status (see figure below)
V7.15 DO1, RO2, RO3 — Digital and relay output status (see figure below)
V7.16 Analog I
out
mA Current output at terminals AO1+ and AO1–
V1.13
DIN1,DIN2, DIN3
OFF ON
OFF
V1.14
DIN4,DIN5, DIN6
ON OFF
OFF
V1.15
DO1, RO1, RO2
OFF OFF
ON