Installation Manual
Menu Information
9000X AF Drives MN04001004E—May 2011 www.eaton.com 33
Keypad Control Menu (M2)
In the Keypad Control Menu, you can set the frequency
reference, choose the motor direction for keypad operation,
and determine if the STOP button will be active at all times.
See figure below.
M2 Keypad Control Menu
Note
This parameter number varies for different applications.
M2 Keypad Control
R2.1 Keypad Reference
P2.2 Keypad Direction
. . .
P2.x Stop Button Active
R2.1
Keypad
Reference
Range: Min. Frequency—Max. Frequency
Units: Hertz
Keypad Reference
This displays and allows the operator to edit the keypad frequency reference. A change takes place immediately. This reference value
will not influence the output frequency unless the keypad has been selected as the active control place.
P2.2
Keypad
Direction
Range: Forward, Reverse Default: Forward
Keypad Direction
This allows the operator to change the rotation direction of the motor. This setting will not influence the rotation direction of the motor
unless the keypad has been selected as the active control place.
P2.3
Stop Button
Active
Range: Yes, No Default: Yes
StopButtonActive
By default, pushing the STOP button will always stop the motor regardless of the selected control place. If this parameter is set to No,
the STOP button will stop the motor only when the keypad has been selected as the active control place.