Installation Manual
Control Wiring
26 9000X AF Drives MN04001004E—May 2011 www.eaton.com
Wiring Option Board A2
Option Board A2 Wiring Diagram
Option Board A2 Terminal Descriptions
Option Board A2 Terminal Locations
Terminal Signal Technical Information
21 RO1/1 Normally closed (NC) Switching capacity:
24 Vdc/8A
250 Vac/8A
125 Vdc/0.4A
Min switching load: 5V/10 mA
Continuous capacity: <2 Arms
22 RO1/2 Common
23 RO1/3 Normally open (NO)
24 RO2/1 Normally closed (NC) Switching capacity:
24 Vdc/8A
250 Vac/8A
125 Vdc/0.4A
Minimum switching load: 5V/10 mA
Continuous capacity: <2 Arms
25 RO2/2 Common
26 RO2/3 Normally open (NO)
26
25
24
23
22
21
RO1/1
RO1/2
RO1/3
RO2/1
RO2/2
RO2/3
R
L
Switching:
<8A/24 Vdc
<8A/250 Vac
<0.4A/125 Vdc
Continuously
<2 Arms
AC/DC
Basic Relay Board A2
21
22 2
3
24
25
2
6