Installation Manual

Power Wiring
12 9000X AF Drives MN04001004E—May 2011 www.eaton.com
Power Connection Tightening Torque
Installation Instructions
1. Strip the motor and input power cables as shown in the
figure below and the table on Page 13.
Input Power and Motor Cable Stripping and Wire Lengths
Note
The isolation standoff of the bus bar will not withstand the listed tightening torque.
Use a wrench to apply a counter torque when tightening.
Rating
Frame
Size
Tightening
Torque (in-lbs)
Tightening
Torque (Nm)
230V, 3/4–3 hp FR4 5 0.6
480V, 1–5 hp 5 0.6
230V, 5–7-1/2 hp FR5 13 1.5
480V, 7-1/2–15 hp 13 1.5
230V, 10–15 hp FR6 35 4
480V, 20–30 hp 35 4
575V, 2–25 hp 35 4
230V, 20–30 hp FR7 85 10
480V, 40–60 hp 85 10
575V, 30–40 hp 85 10
480V, 75–125 hp FR8 340/187
40/22
575V, 50–75 hp 340/187
40/22
480V, 150–200 hp FR9 340/187
40/22
575V, 100–175 hp 340/187
40/22