Installation Manual
Power Wiring
9000X AF Drives MN04001004E—May 2011 www.eaton.com 11
Cable and Breaker
Sizes—480V Ratings, continued
Cable and Breaker
Sizes—575V Ratings
Notes
The current interrupting of the breaker, up to 100 kAIC, will determine the overall current rating of the combination.
A UL listed breaker must be used.
Based on a maximum environment of 104°F (40°C).
I
H
hp
Frame
Size FLA
Breaker
Current
Wire Size
AWG
Power Ground
Terminal Size
Power Ground
400 FR11 520 700 2 x 500 500 Bus bar Bus bar
500 590 800 4 x 4/0 500 Bus bar Bus bar
550 650 900 4 x 250 600 Bus bar Bus bar
600 FR12 750 1000 4 x 300 600 Bus bar Bus bar
650 820 1000 4 x 300 600 Bus bar Bus bar
700 920 1200 4 x 400 — Bus bar Bus bar
I
H
hp
Frame
Size FLA
Breaker
Current
Wire Size
AWG
Power Ground
Terminal Size
Power Ground
2 FR6 3.3 15 14 14 1/0–14 2–14
3 4.5 15 14 14 1/0–14 2–14
5 7.5 15 14 14 1/0–14 2–14
7-1/2 10 20 12 14 1/0–14 2–14
10 13.5 30 10 12 1/0–14 2–14
15 18 30 10 10 1/0–14 2–14
20 22 40 8 8 1/0–14 2–14
25 27 40 8 8 1/0–14 2–14
30 FR7 34 50 6 8 1/0–14 1/0–10
40 41 60 4 6 1/0–14 1/0–10
50 FR8 52 100 2 6 3/0–4 3/0–4
60 62 100 1 6 3/0–4 3/0–4
75 80 125 1/0 6 3/0–4 3/0–4
100 100 150 3/0 6 3/0–4 3/0–4
125 FR9 125 200 4/0 2 350 kcmil–2x3/0 3/0–4
150 144 250 350 1/0 350 kcmil–2x3/0 3/0–4
200 FR10 208 300 2 x 250 300 kcmil 600 kcmil 600 kcmil
250 261 400 2 x 300 300 kcmil 600 kcmil 600 kcmil
300 325 500 2 x 350 300 kcmil 600 kcmil 600 kcmil
400 FR11 385 500 2 x 300 300 Bus bar Bus bar
450 460 600 2 x 350 350 Bus bar Bus bar
500 502 700 2 x 500 500 Bus bar Bus bar
550 FR12 590 800 4 x 4/0 500 Bus bar Bus bar
600 650 900 4 x 250 600 Bus bar Bus bar
700 750 1000 4 x 300 600 Bus bar Bus bar