Installation Manual

Power Wiring
10 9000X AF Drives MN04001004E—May 2011 www.eaton.com
UL Compatible Cable Selection and Installation with Breaker
Use only copper wire with temperature rating of at least 75°C.
Cable and Breaker
Sizes—230V Ratings
Cable and Breaker
Sizes—480V Ratings
Notes
A UL listed breaker must be used.
Based on a maximum environment of 104°F (40°C).
I
H
hp
Frame
Size FLA
Breaker
Current
Wire Size
AWG
Power
Terminal Size
Ground Power Ground
1 FR4 4.8 15 14 14 12–16 14–16
1-1/2 6.6 15 14 14 12–16 14–16
2 7.8 15 14 14 12–16 14–16
3 11 15 12 12 12–16 14–16
5 FR5 17.5 20 10 10 8–16 8–16
7-1/2 25 30 8 8 8–16 8–16
10 FR6 31 40 8 8 1/0–14 2–14
15 48 60 4 6 1/0–14 2–14
20 FR7 61 80 2 6 1/0–14 2/0–10
25 72 100 2 6 1/0–14 2/0–10
30 87 100 1/0 4 1/0–14 2/0–10
I
H
hp
Frame
Size FLA
Breaker
Current
Wire Size
AWG
Power
Terminal Size
Ground Power Ground
1-1/2 FR4 3.3 15 14 14 12–16 14–16
2 4.3 15 14 14 12–16 14–16
3 5.6 15 14 14 12–16 14–16
5 7.6 15 14 14 12–16 14–16
7-1/2 FR5 12 20 12 12 8–16 8–16
10 16 30 10 10 8–16 8–16
15 23 30 8 8 8–16 8–16
20 FR6 31 40 8 8 1/0–14 2–14
25 38 50 6 8 1/0–14 2–14
30 46 60 4 6 1/0–14 2–14
40 FR7 61 80 2 6 1/0–14 2/0–10
50 72 100 2 6 1/0–14 2/0–10
60 87 100 1/0 4 1/0–14 2/0–10
75 FR8 105 125 2/0 2 3/0–4 3/0–4
100 140 150 4/0 1/0 350 kcmil–3/0 3/0–4
125 170 200 300 2/0 350 kcmil–3/0 3/0–4
150 FR9 205 250 350 3/0 350 kcmil–2 x 3/0 3/0–4
200 261 300 2 x 250 3/0 350 kcmil–2 x 3/0 3/0–4
250 FR10 300 400 2 x 250 300 kcmil 600 kcmil 600 kcmil
300 385 500 2 x 300 300 kcmil 600 kcmil 600 kcmil
350 460 600 2 x 400 300 kcmil 600 kcmil 600 kcmil