Installation Manual

Power Wiring
9000X AF Drives MN04001004E—May 2011 www.eaton.com 9
Cable and Bus Bar Sizes, SPX FR10–FR12—575V Ratings
Cable and Bus Bar Sizes, SPX FR13–FR14—575V Ratings
Notes
90°C rating recommended.
Rigid copper connection.
I
H
hp
Frame
Size Current
Internal Power Cables
External Power Bus Bars
Cu (per Phase) Cu (in Inches) Qty.
200 FR10 208 2 x 2/0 1.18 x 0.25 3
250 261 2 x 2/0 1.18 x 0.25 3
300 325 2 x 2/0 1.18 x 0.25 3
400 FR11 385 2 x 3/0 1.57 x 0.25 3
450 460 2 x 3/0 1.57 x 0.25 3
500 502 2 x 2 x 2/0 1.18 x 0.25 6
FR12 590 2 x 2 x 2/0 1.18 x 0.25 6
600 650 2 x 2 x 2/0 1.18 x 0.25 6
700 750 2 x 2 x 2/0 1.18 x 0.25 6
I
H
hp
Frame
Size Current
Internal Power Connections Supply Bus Bars
Bus Bar Size
NFE–INU
(in Inches)
Bus Bar Size/
Phase
(Choke—NFE)
(in Inches)
Cable Size/
Phase
(Choke—NFE)
Cu
(in Inches) Qty.
800 FR13 820 2.36 x 0.39 1.57 x 0.25 2 x 300 kcmil 1.18 x 0.25 6
900 920 2.36 x 0.39 1.57 x 0.25 2 x 250 kcmil 1.18 x 0.25 6
1000 1030 2.36 x 0.39 1.57 x 0.25 2 x 300 kcmil 1.18 x 0.25 6
1350 FR14 1300 3.15 x 0.39 1.57 x 0.25 2 x 250 kcmil 1.18 x 0.25 12
1500 1500 2.36 x 0.39 1.57 x 0.25 2 x 250 kcmil 1.18 x 0.25 12
2000 1900 2.36 x 0.39 1.57 x 0.25 2 x 300 kcmil 1.18 x 0.25 12