Installation Manual
Power Wiring
6 9000X AF Drives MN04001004E—May 2011 www.eaton.com
UL Compatible Cable Selection and Installation
Use only copper wire with temperature rating of at least 75°C.
40°C Cable and Fuse Sizes—230V Ratings
40°C Cable and Fuse Sizes—480V Ratings
Note
UL recognized type JJS is preferred but RK is acceptable.
I
L
hp
Frame
Size
NEC I
(A)
I
(A)
Fuse
Quantity
Fuse
(A)
Wire Size
AWG
Power Ground
Terminal Size
Power Ground
1 FR4 4.2 4.8 3 10 14 14 16–12 16–14
1-1/2 6 6.6 3 10 14 14 16–12 16–14
2 6.8 7.8 3 10 14 14 16–12 16–14
3 9.6 11 3 15 14 14 16–12 16–14
5 FR5 15.2 17.5 3 20 12 12 16–8 16–8
7-1/2 22 25 3 30 10 10 16–8 16–8
10 28 31 3 40 8 8 16–8 16–8
15 FR6 42 48 3 60 4 8 14–1/0 10–2
20 54 61 3 80 2 6 14–1/0 10–2
25 FR7 68 72 3 100 2 6 14–1/0 10–2/0
30 80 87 3 110 1 6 14–1/0 10–2/0
40 104 114 3 125 1/0 4 14–1/0 10–2/0
50 FR8 130 140 3 175 3/0 2 4–3/0 4–3/0
60 154 170 3 200 4/0 I/0 3/0–350 kcmil 4–3/0
75 192 205 3 250 300 2/0 3/0–350 kcmil 4–3/0
100 FR9 248 261 3 300 2 x 4/0 3/0 2 x 3/0–350 kcmil 4–3/0
I
L
hp
Frame
Size
NEC I
(A)
I
(A)
Fuse
Quantity
Fuse
(A)
Wire Size
AWG
Power Ground
Terminal Size
Power Ground
1-1/2 FR4 3 3.3 3 10 14 14 16–12 16–14
2 3.4 4.3 3 10 14 14 16–12 16–14
3 4.8 5.6 3 10 14 14 16–12 16–14
5 7.6 7.6 3 10 14 14 16–12 16–14
7-1/2 11 12 3 15 12 14 16–12 16–14
10 FR5 14 16 3 20 10 12 16–8 16–8
15 21 23 3 30 10 10 16–8 16–8
20 27 31 3 35 8 8 16–8 16–8
25 FR6 34 38 3 50 6 8 14–1/0 10–2
30 40 46 3 60 4 8 14–1/0 10–2
40 52 61 3 80 2 6 14–1/0 10–2
50 FR7 65 72 3 100 2 6 14–1/0 10–2/0
60 77 87 3 110 1 6 14–1/0 10–2/0
75 96 105 3 125 1/0 4 14–1/0 10–2/0
100 FR8 124 140 3 175 3/0 2 4–3/0 4–3/0
125 156 170 3 200 4/0 I/0 3/0–350 kcmil 4–3/0
150 180 205 3 250 300 2/0 3/0–350 kcmil 4–3/0