Installation Manual

Troubleshooting Charts Using Fault Codes
9000X AF Drives MN04001004E—May 2011 www.eaton.com 97
F15—Motor Stalled
F15?
No
Y
es
No
Measured current =
Monitored current?
Y
es
Measure actual motor current and
compare it to V1.4 reading
Combination of the rating for motor and
drive do not match with mechanical load
F15
Check parameters in G2.7 and
make corrections to match
with requirements of application
Check mechanical load of the application
versus rating of the motor and the drive
Clear fault memory
Check current measuring circuit
according to instructions in service manual
and replace defective parts
as recommended in spare parts lists