Installation Manual
Control Wiring
9000X AF Drives MN04001004E—May 2011 www.eaton.com 25
Option Board A9 Jumper Location and Settings
CMB and CMA Internally
Connected and Isolated
from Ground
X1 Jumper Setting
Analog Input 1 (AI1)
X2 Jumper Setting
Analog Input 2 (AI2)
X6 Jumper Setting
Analog Output 1 (A01)
X3 Jumper Setting
CMA and CMB Grounding
0 to 10V*
Voltage Input
–10 to 10V
Voltage Input
4 to 20 mA
Current Input
0 to 10V
(Differential)
Voltage Input
CMB Connected to Ground*
CMA Connected to Ground
CMB Isolated from Ground
CMA Isolated from Ground
* Designates Default Jumper Settings
4 to 20 mA*
Current Input
0 to 10V
Voltage Input
0 to 10V
(Differential)
Voltage Input
–10 to 10V
Voltage Input
0(4) to 20 mA*
Current Output
0 to 10V
Voltage Output
A
B
C
D
A
B
C
D
A
B
C
D
X1
X3
X2 X6
A
B
CD
A
B
CD
A
B
CD
A
B
CD
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
CD