Firmware Manual
9000X AF Drives
6-24 For more information visit: www.eaton.com
MN04004001E
August 2010
Multi-Purpose Control Application
Autorestart Parameters (Control Keypad: Menu M1
➔
G1.8)
Table 6-25: Autorestart Parameters — G1.8
Fieldbus Parameters (Control Keypad: Menu M1
➔
G1.9)
Table 6-26: Fieldbus Parameters — G1.9
Code Parameter Min. Max. Unit Default Cust ID Note
P1.8.1 Wait time 0.10 10.00 s 0.50 717
P1.8.2 Trial time 0.00 60.00 s 30.00 718
P1.8.3 Start mode 0 2 0 719 0 = Ramp
1 = Flying start
2 = According to par. 1.4.6
P1.8.4 Number of tries
after undervoltage
trip
0 10 0 720
P1.8.5 Number of tries
after overvoltage
trip
0 10 0 721
P1.8.6 Number of tries
after overcurrent
trip
0 3 0 722
P1.8.7 Number of tries
after reference trip
0 10 0 723
P1.8.8 Number of tries
after motor
temperature fault
trip
0 10 0 726
P1.8.9 Number of tries
after external fault
trip
0 10 0 725
P1.8.10 Number of tries
after underload
fault trip
0 10 1 738
Code Parameter Min. Max. Unit Default Cust ID Note
P1.9.1 Fieldbus min scale 0.00 320.00 Hz 0.00 850
P1.9.2 Fieldbus max
scale
0.00 320.00 Hz 0.00 851
P1.9.3 Fieldbus data out 1
selection
0 10000 1 852 Choose monitoring data with
parameter ID
P1.9.4 Fieldbus data out 2
selection
0 10000 2 853 Choose monitoring data with
parameter ID
P1.9.5 Fieldbus data out 3
selection
0 10000 3 854 Choose monitoring data with
parameter ID
P1.9.6 Fieldbus data out 4
selection
0 10000 4 855 Choose monitoring data with
parameter ID
P1.9.7 Fieldbus data out 5
selection
0 10000 5 856 Choose monitoring data with
parameter ID
P1.9.8 Fieldbus data out 6
selection
0 10000 6 857 Choose monitoring data with
parameter ID